MEASUREMENT AND ANALYSIS OF ELECTRIC AND MAGNETIC FIELD STRENGTH IN GRID-TIED PHOTOVOLTAIC POWER SYSTEM COMPONENTS

[ X ]

Tarih

2021

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

Oxford Univ Press

Erişim Hakkı

info:eu-repo/semantics/closedAccess

Özet

In this study, electric field and magnetic field strengths at 50 Hz are measured in a solar power plant located far from residential areas, and the measurement results near various sources of the electric and magnetic fields in the power plant are presented. Although the measured values for the electric field caused by the solar panel range between 0.07 and 1.33 V/m, the measured values for the magnetic field by the solar panel range between 0.037 and 0.19 mu T. In front of the inverter, the measured value of the electric field reaches 0.7 V/m, whereas the measured value of the magnetic field reaches 2.2 mu T. The results are presented and evaluated in light of the exposure limits to electromagnetic fields published by international organisations.

Açıklama

Anahtar Kelimeler

Exposure

Kaynak

Radiation Protection Dosimetry

WoS Q Değeri

Q4

Scopus Q Değeri

Q3

Cilt

194

Sayı

1

Künye