MEASUREMENT AND ANALYSIS OF ELECTRIC AND MAGNETIC FIELD STRENGTH IN GRID-TIED PHOTOVOLTAIC POWER SYSTEM COMPONENTS
[ X ]
Tarih
2021
Dergi Başlığı
Dergi ISSN
Cilt Başlığı
Yayıncı
Oxford Univ Press
Erişim Hakkı
info:eu-repo/semantics/closedAccess
Özet
In this study, electric field and magnetic field strengths at 50 Hz are measured in a solar power plant located far from residential areas, and the measurement results near various sources of the electric and magnetic fields in the power plant are presented. Although the measured values for the electric field caused by the solar panel range between 0.07 and 1.33 V/m, the measured values for the magnetic field by the solar panel range between 0.037 and 0.19 mu T. In front of the inverter, the measured value of the electric field reaches 0.7 V/m, whereas the measured value of the magnetic field reaches 2.2 mu T. The results are presented and evaluated in light of the exposure limits to electromagnetic fields published by international organisations.
Açıklama
Anahtar Kelimeler
Exposure
Kaynak
Radiation Protection Dosimetry
WoS Q Değeri
Q4
Scopus Q Değeri
Q3
Cilt
194
Sayı
1